Specifications
AL1024ULXB2 Power Supply/Charger
Input
- Voltage: 115VAC, 60Hz, 4.2A max.
- Input Fuse: 5A / 250V.
Outputs
- Voltage: 24VDC.
- Current: 10A @ 24VDC continuous max.
- Protection: Overvoltage protection. Filtered and regulated.
Battery Charging
- Capacity: 12AH /12VDC (2 within enclosure); 40 AH / 65 AH (requires separate enclosure).
- Type: Sealed lead acid or gel type.
- Failover: Upon AC loss, instantaneous.
- (Batteries are sold separately).
Supervision
- AC Failure: Form “C” contacts.
- Battery: Form “C” contacts.
Indicators LED
- Input: 115VAC is present.
- DC Output: Powered.
- Battery: Discharged or not connected.
VR6 Voltage Regulator
Input
- Voltage: 24VDC from AL1024ULXB2.
Output
- Voltage: 12VDC.
- Current: 6A continuous.
- Other: Surge suppression.
Indicators LED
- Input: 24VDC is present.
- Output: Powered.
LINQ8PDCB Network Power Distribution Module
Input
- Voltage: 24VDC from AL1024ULXB2 and 12VDC from VR6.
- Input Fuses: 15A/32V.
Outputs
- Eight (8) PTC protected outputs rated 2A.
- Power output(s) can be locally or remotely controlled.
- Surge suppresion.
- Output PTCs: 2A.
Status Monitoring
- Power Supply output voltage and load.
- Voltage and load of each output.
- FACP trigger and reset status.
- Unit temperature (Celsius).
- Power Supply AC and Battery status.
- Battery health.
Indicators (LED)
- Bat Local: Charging current status.
- FACP: Triggered / Released.
- Input: Input signal.
- Out1 - Out8: Bi-colored LEDs indicate 12 or 24VDC.
Reporting
- Windows Dashboard Alert messages.
- E-mail notifications.
- Event Log tracks history.
Programming Features
- Power Supply(ies) voltage and load limits (High/Low).
- FACP trigger type (wet or dry-N.O./N.C.).
- Input Function (FACP reset/tamper).
- Output Reset Trigger (N.O./N.C.).
Battery Monitor Configuration:
- - Battery condition (Low/Normal/Missing).
- - Service Date.
- Configurable Output Relay(s).
Individual Output Configuration:
- - Device ID.
- - Voltage and Current Limits (High/Low).
- - FACP Trigger Setting (latching/non-latching/inactive).
- - Battery Backup.
Fire Alarm Interface
- Supervised FACP disconnect (Latching or Non-Latching).
- FACP reset (N.C. or N.O.).
Environmental
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Accommodates up to two (2) 12VDC/12AH Batteries.
- Dimensions 12"W x 15.5"H x 4.5"D (304.8 mm W x 393.7 mm H x 114.3 mm D).
- 1.125" and 1.375" combination knockouts.
Weights (approximate):
- Product Weigtht: 9.4 Lbs. (4.26 kg).
- Shipping Weigtht: 10.5 Lbs. (4.76 kg).