Specifications
Input
- Power input 220VAC (working range 198VAC - 256VAC), 50/60 Hz, 2.2A.
- Two (2) Class A, Style Z or two (2) Class B, Style W, Y FACP inputs.
- Two (2) NC dry contact trigger inputs.
Output
- Class 2 Rated power limited outputs.
- 24VDC voltage regulated power limited outputs.
- 10A max total alarm current.
- 2.5A max current per output.
- Two auxiliary outputs rated at 1A each (1A continuous, 1A AC disconnect).
Programmable supervised indicating circuit outputs:
- Four (4) Class B, Style W, Y or Four (4) Class A, Style Z or Two (2) Class A, Style Z and Two (2) Class B, Style W, Y.
- Thermal and short circuit protection with auto reset.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switchover to stand-by battery when AC fails.
- Zero voltage drop when switching over to battery backup.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contact, 1A / 28VDC).
- Factory set for 30 seconds with optional 2.5 to 3 hour delay setting (field selectable).
- Instant local AC trouble reporting relay (form "C" contact, 1A / 28VDC).
- Battery presence and low battery supervision (form "C" contact, 1A / 28VDC).
Visual Indicators
- Input and output status LED indicators.
Special Features
- 2-wire horn/strobe Sync mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
- Sync protocols include Potter/Amseco, Faraday, Gentex°, System Sensor°, and CooperWheelock°.
- Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit).
- Compatible with 12VDC or 24VDC fire panels.
- Output loop supervision directed to input 1 or input 2.
- Signal Circuit Trouble Memory - facilitates quick identification of an intermittent/fault (short circuit, open or ground) which has previously occurred on one or more signaling circuit outputs. LEDs indicate/ identify which output the fault has occurred.
- Common trouble input and output.
- Ground fault detection.
Added Features
- Unit includes power supply, logic board enclosure, cam lock, and battery leads.
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70°C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
- BTU/Hr. (approx.): 31 BTU/Hr.
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Dimensions 14.5"W x 18"H x 4.62"D (368 mm W x 457 mm H x 118 mm D).
- 1/2" and 3/4" combination knockouts.
Weights (approximate):
- Product Weigtht: 14.8 Lbs. (6.71 kg).
- Shipping Weigtht: 19.15 Lbs. (8.69 kg).