Specifications
Input
- Input 220VAC (working range 198VAC - 256VAC), 50/60Hz, 0.3A.
- Access control trigger input.
Output
- 12VDC or 24VDC selectable outputs.
- 1A supply current.
- Two (2) outputs.
- Fail-Safe/Fail-Secure lock output (switched).
- Auxiliary power output (unswitched).
- PTC protected outputs, rated @ 2.5A.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current: 400mA.
- Automatic switch over to stand-by battery when AC fails.
- (Batteries are sold separately).
Supervision
- Supervised Fire Alarm Disconnect (Latching w/reset or Non-Latching).
Indicator (LED)
- Unit Status: Normal / No Output / Loss of AC / Triggered.
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70ºC ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
- 12VDC: 6 BTU/Hr.
- 24VDC: 6 or 12 BTU/Hr.
- System AC input VA requirement: 66VA.
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).
- 1/2" and 3/4" combination knockouts.
Weights (approximate):
- Product Weigtht: 9.5 Lbs. (4.31 kg).
- Shipping Weigtht: 10.4 Lbs. (4.72 kg).