Specifications
Input
- Nominal 220VAC (working range 198VAC - 256VAC), 50/60Hz, 1.7A.
- Input fuse rated @ 5A/250V.
Output
- 12VDC or 24VDC selectable output.
- 12VDC or 24VDC @ 2.5A supply current.
- Four (4) fuse protected outputs.
- Outputs are rated @ 15A/32V.
- Filtered and electronically regulated outputs.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
Supervision
- AC fail supervision (form "C" contacts).
- Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
- Low battery supervision (form "C" contacts).
- Battery presence supervision (form "C" contacts).
Visual Indicators
- AC input and DC output LED indicators.
Electrical
Temperature:
- Operating Temperature: 0° C to 49° C (32° F to 120° F).
- Storage Temperature: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/-5%.
BTU/Hr. (approx.):
- 12VDC: 15 BTU/Hr.
- 24VDC: 31 BTU/Hr.
- System AC input VA requirement: 402.5VA.
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Accommodates up to two (2) 12VDC/7AH Batteries.
- Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).
- 1/2" and 3/4" combination knockouts.
Weights (approximate):
- Product Weigtht: 6.8 Lbs. (3.1 kg).
- Shipping Weigtht: 8.6 Lbs. (3.9 kg).