Power Supply Charger, 8 PTC Class 2 Outputs, 12/24VDC @ 2.5A, 115VAC, BC300 Enclosure
AL300ULPD8CB is a multi-output power supply/charger that converts a 115VAC/60Hz input into eight (8) Class 2 Rated 12VDC or 24VDC power limited outputs.
Specifications
Input
Input 115VAC, 60Hz, 3.5A.
Input fuse rated @ 3.5A/250V.
Output
12VDC or 24VDC selectable output.
Burglar Alarm Applications (UL 603):
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
12VDC or 24VDC @ 2.5A supply current.
Eight (8) Class 2 Rated PTC protected power limited outputs (auto-resettable).
Outputs are rated @ 2.5A.
Filtered and electronically regulated outputs.
Short circuit and thermal overload protection.
Battery Charging
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
Maximum charge current: 0.7A.
Zero voltage drop when switched over to battery backup.
(Batteries are sold separately).
Supervision
AC fail supervision (form "C" contacts).
Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
Low battery supervision (form "C" contacts).
Battery presence supervision (form "C" contacts).
Visual Indicators
AC input, DC output and Battery LED indicators.
Electrical
Temperature:
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity: 85% +/-5%.
BTU/Hr. (approx.):
12VDC: 15 BTU/Hr.
24VDC: 31 BTU/Hr.
System AC input VA requirement: 402.5VA.
Agency Listings
UL Listed For:
Power Supplies for use with Burglar Alarm Systems (UL603)
Access Control System Units (UL294)
Hospital Signaling and Nurse Call Equipment (UL1069)
Power Supplies for Fire Protective Signaling Systems (UL1481)
cUL Listed For:
CSA Standard C22.2 No.205-M1983, Signal Equipment
NFPA 72 Compliant
Dimensions & Weight
Enclosure:
Wall mount enclosure for indoor use.
Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).