Specifications
Input
- 16VAC to 24VAC, 20VA to 40VA.
Output
- Switch selectable 6VDC-12VDC-24VDC.
- 6VDC or 12VDC @ 1.2A supply current or 24VDC @ 0.75A supply current.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Maximum charge current: 0.3A.
- PTC battery protection.
- (Batteries are sold separately).
Visual Indicators
- AC input and DC output LED indicators.
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr.:
- 6VDC: 4 BTU/Hr.
- 12VDC: 7 BTU/Hr.
- 24VDC: 9 BTU/Hr.
- System AC input VA requirement:
- 16.5VAC/20VA: 138. 16.5VAC/40VA: 276.
- 24VAC/20VA: 92. 24VAC/40VA: 192.05.
Dimensions & Weight
Dimensions (approximate):
- 2.5"W x 3"L x 1.5"H (63.5 mm W x 76.2 mm L x 38.1 mm H).
Weights (approximate):
- Product Weigtht: 0.1 Lbs. (0.05 kg).
- Shipping Weigtht: 0.15 Lbs. (0.07 kg).