Specifications
eFlow6NB Power Supply/Charger
Input
- Voltage: 120VAC, 60Hz, 3.5A max.
- Main Fuse: 5A / 250V.
Output
- Voltage: 12VDC or 24VDC selectable.
- Current: 6A continuous.
Outputs
- Auxiliary: Class 2 power-limited @ 1A (unswitched).
- Other: Overvoltage protection. Filtered and regulated.
Battery Charging
- Type: Sealed lead acid or gel type.
- Fuse Rating: 10A/32VDC.
- Failover: Upon AC loss, instantaneous.
- (Batteries are sold separately).
Fire Alarm Disconnect
- Supervised: Latching or non-latching.
- EOL: 10K Resistor.
Supervision
- AC Failure: Form “C” contacts.
- Battery: Form “C” contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units or 71-73% for 12V units. Prevents deep battery discharge.
Indicators (LED)
- AC Input: 120VAC is present.
- DC Output: Powered.
PD8UL Power Distribution Module
Input
- Voltage: 12VDC or 24VDC from eFlow6NB.
Outputs
- Voltage: 12VDC or 24VDC.
- Eight (8) fuse protected outputs.
- 3.5A per output max.
- Output Fuses: 3.5A/32VDC.
Indicators (LED)
ACM8 Access Power Controller
Input
- Voltage: 12VDC or 24VDC from eFlow6NB.
- Main Fuse: 10A / 32V.
Outputs
- Voltage: 12VDC or 24VDC.
- Eight (8) independently controlled fused outputs:
- a) Fail-Safe and/or Fail-Secure power outputs.
- Form “C” Relays rated 28VAC or VDC @ 2.5A.
- b) Auxiliary power outputs (unswitched).
- c) Any combination of the above.
- Output Fuses: 3.5A / 32VDC.
Indicators (LED)
- Red LEDs: Outputs are triggered (relays energized).
- Green LED: FACP disconnect is triggered.
Environmental
Temperature
- Operating: 0° C to 50° C (32° F to 122° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
BTU/Hr. (approx.):
- 12VDC: 41 BTU/Hr.
- 24VDC: 77 BTU/Hr.
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Dimensions 16.5"W x 20.5"H x 6.25"D (419.1 mm W x 520.7 mm H x 158.8 mm D).
Weights (approximate):
- Product Weigtht: 26.9 Lbs. (12.2 kg).