Specifications
Input
- 220VAC (working range 198VAC - 256VAC), 50/60Hz, 1.0A.
- Normally closed [NC] or normally open [NO] dry contact inputs (switch selectable).
Outputs
- 12VDC or 24VDC @ 6A total output current.
- Sixteen (16) fuse protected outputs.
- Maximum current per ACM8R-M output is 2.5A.
- Individually selectable Mag Lock/Strike (Fail-Safe, Fail-Secure) solid state fuse protected outputs.
- Thermal and short circuit protection with auto reset.
Fire Alarm Interface
- Latching or Non-Latching fire alarm reset switch individually selectable for each output.
- Remote reset capability for latching Fire Alarm Interface mode.
Fire Alarm disconnect input options:
- a) Normally open [NO] or normally closed [NC] dry contact input.
- b) Polarity reversal input from FACP signaling circuit.
Visual Indicators
- Individual Output Status LEDs located on the front panel.
Battery Charging
- Type: Sealed lead acid or gel type.
- Failover: Upon AC loss, instantaneous.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contacts).
- Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
- Low battery and battery presence supervision (form "C" contact).
Additional Features
- Removable terminal blocks with locking screw flange.
- 3-wire line cord.
- Illuminated master power disconnect circuit breaker with manual reset.
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
- 12VDC: 37 BTU/Hr.
- 24VDC: 74 BTU/Hr.
Dimensions & Weight
Enclosure:
- Modular 2U standard EIA 19" rack mount chassis.
- Dimensions 19.12"W x 3.25"H x 8.5"D (486 mm W x 83 mm H x 216 mm D).
- Allow 1/2U space on top and bottom of the unit for ventilation.
Weights (approximate):
- Product Weigtht: 11.7 Lbs. (5.307 kg).
- Shipping Weigtht: 12.7 Lbs. (5.76 kg).