Specifications
Input
- Universal input 115VAC, 50/60Hz, 0.95A or 230VAC, 50/60Hz, 0.6A.
- Input fuse rated @ 5A/250V.
Output
- DC1: 12VDC or 24VDC @ 3A.
- DC2: 12VDC @ 1A.
- Note: If DC2 is not used, DC1 rating is 12VDC or 24VDC rated @ 4A max.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current 0.7A.
- Automatic switch over to stand-by battery when AC fails.
- Battery leads included.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contacts).
- Low battery supervision (form "C" contacts).
Visual Indicators
- AC input and DC output LED indicators.
Features
- Power ON/OFF switch (interrupts mains).
Electrical
Temperature:
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
- 12VDC: 25 BTU/Hr.
- 24VDC: 49 BTU/Hr.
System AC input VA requirement:
- 115VAC: 109.25VA.
- 230VAC: 138VA.
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Accommodates up to two (2) 12VDC/7AH Batteries.
- Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).
- 1/2" and 3/4" combination knockouts.
Weights (approximate):
- Product Weigtht: 7.4 Lbs. (3.36 kg).
- Shipping Weigtht: 8.3 Lbs. (3.76 kg).