Specifications
Input
- Universal input 115VAC, 50/60Hz, 0.95A or 230VAC, 50/60Hz, 0.6A.
Output
- 12VDC or 24VDC selectable output.
- 2.5A continuous supply current.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Battery Charging
- Built-in charger for sealed lead acid or gel type batteries.
- Maximum charge current 0.5A.
- Automatic switch over to stand-by battery when AC fails.
- Battery leads included.
- (Batteries are sold separately).
Supervision
- AC fail supervision (form "C" contacts).
- Low battery supervision (form "C" contacts).
Visual Indicators
- AC input and DC output LED indicators.
Features
Electrical
Temperature:
- Operating: - 20° C to 49° C (-4 ° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
- 12VDC: 15 BTU/Hr.
- 24VDC: 31 BTU/Hr.
System AC input VA requirement:
- 115VAC: 109.25VA.
- 230VAC: 138VA .
Dimensions & Weight
Dimensions (approximate):
- 4.5"W x 7.25"L x 1.75"H (114.3 mm W x 184.1 mm L x 44.5 mm H).
Weights (approximate):
- Product Weigtht: 0.65 Lbs. (0.29 kg).
- Shipping Weigtht: 0.85 Lbs. (0.38 kg).