Specifications
Input
- Input 220VAC 60Hz, 4A.
- Two (2) NO trigger inputs.
- Input fuse rating: 6.3A.
Outputs
Power options:
- Two (2) 20VDC to 26.4VDC individually controlled lock outputs for applications with battery back-up. 24VDC for applications without battery back-up (US applications only). Current rating 16A for 300ms, 0.75A continuous supply current.
- 5V holding voltage with 20VDC to 26.4VDC initial 100ms pulse. Maximum total 5V holding current of both outputs is 0.74A.
- One (1) 20VDC to 26.4VDC for applications with battery back-up, 24VDC for applications in US not requiring battery back-up. Auxiliary output rated @ 0.75A continuous supply current (Not affected by FACP trigger).
- One (1) 12VDC filtered regulated auxiliary output rated @ 0.75A in alarm, 0.5A stand-by current (Not affected by FACP trigger).
- Two (2) follower form "C" relay outputs rated @ 0.6A/28VDC. Relays energize while input is closed.
- Two (2) delayed follower Normally Open relay outputs rated @ 0.6A/28VDC. Delay time is selectable 0.5 seconds or 1 second. Energized duration is 1 second.
- Trouble relay output indicating low DC output voltage.
Battery Charging
- Battery leads included.
- Battery fuse rating: 25A/32V.
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- When 7AH batteries are used, battery capacity for emergency stand-by is 30 minutes.
- (Batteries are sold separately).
Visual Indicators
- Green AC Power LED indicates 220VAC present.
- Green trigger input LEDs indicate panic device status/trouble (activated, short or open circuit).
- Red Fire Alarm Interface (FAI) LED indicates FACP disconnect is activated.
- Red Battery LED indicates low battery during AC failure and manual test.
- Green AC LED indicates loss of AC trouble (not active during manual test sequence).
Fire Alarm Disconnect
- Normally Closed FACP trigger input.
- Programmable Fire Alarm Disconnect options:
- Removes power to outputs and disables delayed follower relays.
- Connects power to lock outputs and enables delayed follower relays.
Features
- Manual testing to allow to tests battery conditions.
- Adjustable panic release from 1 sec. to 30 secs.
- Note: Follower and Delay relay turns off when the potentiometer selected time elapses after release of the input trigger.
- Cam lock included.
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70ºC ( - 4° F to 158° F).
- Relative Humidity: 85% +/- 5%.
- BTU/Hr. (approx.): 197 BTU/Hr.
- System AC input VA requirement: 880VA.
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Accommodates up to two (2) 12VDC/7AH Batteries.
- Dimensions 13"W x 13.5"H x 3.25"D (330 mm W x 343 mm H x 83 mm D).
- 1/2" and 3/4" combination knockouts.
Weights (approximate):
- Product Weigtht: 13.7 Lbs. (6.21 kg).