T1KE38V

8-Door Altronix/Kisi Access and Power Integration Kit - Trove1DR1 with AL600XB220, (2) ACM4

News Flash… Altronix lead time for all Trove Access & Power Integration kits are now 15 days max.

Altronix T1KE38V kit consists of Trove1 enclosure and TDR1 Altronix & Kisi backplane with 12VDC or 24VDC (factory set at 24VDC) @ 6A power supply/charger and two (2) four (4) fuse protected output access control modules. This kit also accommodates various combinations of Kisi boards for up to eight (8) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

  • AL600XB220 Power Supply/Charger
      • Input
        • Voltage: 220VAC (range 198VAC-256VAC), 50/60Hz, 1.5A. max.
        • Input Fuse: 5A / 250V.
      • Outputs
        • Voltage: 12VDC or 24VDC selectable.
        • Current: 6A @ 12VDC or 24VDC continuous max.
        • Other: Filtered and regulated.
  • Battery Charging
    • Capacity: 7AH / 12VDC (Up to 2 within enclosure); 12AH / 12VDC (requires separate enclosure); 40 AH / 65 AH (requires separate enclosure)
    • Type: Sealed lead acid or gel type
    • Failover: Upon AC loss, instantaneous
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators LED
    • Input: 220VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • Two (2) ACM4 Access Power Controllers
      • Input
        • Voltage: 24VDC from AL600XB220.
        • Input Fuse: 10A / 32V.
      • Outputs
        • Voltage: 24VDC.
        • Four (4) independently controlled 2.5A outputs:
        • a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
        • b) Four (4) dry form “C” 5A rated relay outputs.
        • c) Any combination of the above.
        • Four (4) auxiliary power outputs (unswitched).
      • Outputs Ratings
        • Fuses: 3A/32VDC.
      • Indicators (LED's)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 87 BTU/Hr.
 
CE Compliant
 
Components of this Trove kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to two (2) 12VDC/7AH Batteries.
  • Dimensions 14.5"W x 18"H x 4.62"D (368.3 mm W x 457.2 mm H x 118 mm D).
  • 1", 3/4" and 1 1/2" knockouts.
Weights (approximate):
  • Product Weight: 17.23 Lbs. (7.82 kg).
  • Shipping Weight: 21.23 Lbs. (9.53 kg).

Access controllers not included

*Batteries sold separately