T2CVK33F10

10-Door Altronix/CDVI Access and Power Integration Kit - Trove2CV2 with 2-eFlow6NB, 2-MOM5

Altronix T2CVK33F10 kit consists of Trove2 enclosure, TCV2 CDVI/Altronix backplane with two (2) 12 or 24VDC @ 6A power supply/chargers, and two (2) PTC protected five (5) output Power Distribution Modules with Fire Alarm Interface. This kit also accommodate various combinations of CDVI Atrium A22K/A22NB/ADH10 boards for up to ten (10) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

Specifications

  • Two (2) eFlow6NB Power Supply/Chargers
      • Input
        • Voltage: 120VAC, 60Hz, 3.5A max.
        • Fusing: 5A / 250V.
      • Output
        • Voltage: 12VDC or 24VDC selectable.
        • Current: 6A continuous max.
        • Auxiliary: Power-limited @ 1A (unswitched).
        • Other: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Type: Sealed lead acid or gel type.
    • Fuse Rating: 10A @ 32VDC.
    • Failover: Upon AC loss, instantaneous.
    • (Batteries are sold separately).
  • Fire Alarm Disconnect
    • Supervised: Latching or non-latching.
    • EOL: 10K Resistor.
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
    • Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
  • Indicators LED
    • Input: 120VAC is present.
    • DC Output: Powered.
  • Two (2) MOM5 Power Distribution Modules with Fire Alarm Interface
      • Input
        • Voltage: 12VDC or 24VDC from power supply.
      • Output
        • Five (5) individual Class 2 Rated PTC protected power-limited outputs (auto-resettable).
        • Voltage: 12VDC or 24VDC.
        • Current: 2.5A continuous supply current. Current limit is 2A per output.
        • Other: Short circuit and thermal overload protection. Filtered and regulated.
      • Fire Alarm Interface
        • Fire Alarm Panel or Access Control System trigger inputs N.O. or N.C. supervised trigger input and polarity reversal trigger input.
      • Supervision
        • Power Failure: Form “C” contact rated 1A 28VDC/115VAC.
        • Trigger: Form “C” contact rated 1A 28VDC/115VAC.
      • Indicators (LED)
        • Input: Power is present.
        • Input Trigger: On.
        • Outputs (Individual LEDs): Output fail.
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 12VDC: 74 BTU/Hr.
        • 24VDC: 148 BTU/Hr.
        • 12VDC and 24VDC: 111 BTU/Hr.

Agency Listings

 
CE Compliant

Accessories

Name Description
WM5 Magnetic Cable Tie Mounts
WM25 Magnetic Cable Tie Mounts
WM100 Magnetic Cable Tie Mounts
MM8 Mounting Magnets, Eight (8) Quantity per Pack
MM4 Mounting Magnets, Four (4) Quantity per Pack
MM24 Mounting Magnets, Twenty Four (24) Quantity per Pack
MM12 Mounting Magnets, Twelve (12) Quantity per Pack
LINQ2 Network Communication Module, Control, Monitor and Report Power Supply Diagnostics, Compatible with eFlow Series and MaximalF Power Supply/Chargers
MM4S Mounting Magnets, Four (4) Quantity per Pack
MM8S Mounting Magnets, Eight (8) Quantity per Pack

Dimensions & Weight

Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weigtht: 54.7 Lbs. (24.8 kg).