T2HWK712D

12-Door Altronix/Honeywell Access and Power Integration Kit - Trove2HW2 with AL1024ULXB2, ACM8CB, ACM4, VR6, PDS8CB

Altronix T2HWK712D kit consists of Trove2 enclosure, THW2 Honeywell/Altronix backplane, THWD2 Honeywell door backplane with one (1) 24VDC @ 10A power supply/charger, one (1) 8-output PTC access power controller, one (1) 4-output PTC access power controller, one (1) voltage regulator and one (1) 8-output dual input power distribution module.
THW2 backplane also accommodates up to three (3) Honeywell 4200 Series or WIN-PAK Series boards and up to one (1) Honeywell PW7K1ICE, PW7K1R1E boards for up to twelve (12) doors in a single enclosure. THWD2 accommodates additional one (1) Honeywell PRO22MX8/PW5K1MX8 and up to six (6) Honeywell 4200 Series or WIN-PAK Series. Trove simplifies board layout and wire management, reduces installation time and labor costs.

Specifications

  • AL1024ULXB2 Power Supply/Charger
      • Input
        • Voltage: 115VAC 60Hz, 4.2A max.
        • Main Fuse: 5A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Current: 10A @ 24VDC continuous max.
        • Other: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Capacity: 12AH /12VDC (2 within enclosure), 40 AH / 65 AH (requires separate enclosure)
    • Type: Sealed lead acid or gel type
    • Failover: Upon AC loss, instantaneous
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators LED
    • Input: 115VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • PDS8CB Dual Input Power Distribution Module
      • Input
        • Voltage: 12VDC from VR6 and 24VDC from AL1024ULXB2.
        • Input PTC: 9A.
      • Outputs
        • Voltage: 12VDC and/or 24VDC.
        • Any of the eight (8) power outputs are selectable to follow power Input 1 or Input 2.
        • Individual outputs may be set to OFF position for servicing.
      • Outputs Ratings
        • PTCs are rated 2.5A.
      • Indicators (LED)
        • DC Output: Eight (8) individual output LEDs.
        • Green: 12VDC
        • Red: 24VDC.
  • VR6 Voltage Regulator
      • Input
        • Voltage: 24VDC from AL1024ULXB2.
      • Output
        • Voltage: 12VDC.
        • Current: 6A continuous.
        • Other: Surge suppression.
      • Indicators LED
        • Input: 24VDC is present.
        • Output: Powered.
  • ACM8CB Access Power Controller
      • Input
        • Voltage: 24VDC from AL1024ULXB2.
        • Main Fuse: 10A / 250V.
      • Outputs
        • Class 2 power-limited auto-resettable outputs.
        • Voltage: 24VDC.
        • Eight (8) 24VDC independently controlled PTC outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
        • b) Any combination of the above.
        • Output PTCs: 2.5A.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • ACM4CB Access Power Controller
      • Input
        • 24VDC from AL1024ULXB2.
        • Input Fuse: 10A/250V.
      • Outputs
        • Class 2 power-limited auto-resettable outputs.
        • Voltage: 24VDC.
        • Four (4) 24VDC independently controlled PTC 2.5A outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs.
        • Form “C” Relays rated 28VAC or VDC @ 2.5A.
        • b) Any combination of the above.
      • Outputs Ratings
        • PTCs: 2.5A.
      • Indicators (LED)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • Environmental
      • Temperature
        • Operating: 0° C to 50° C (32° F to 122° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 128 BTU/Hr.

Agency Listings

 
CE Compliant

Accessories

Name Description
MM12 Mounting Magnets, Twelve (12) Quantity per Pack
MM24 Mounting Magnets, Twenty Four (24) Quantity per Pack
MM4 Mounting Magnets, Four (4) Quantity per Pack
MM8 Mounting Magnets, Eight (8) Quantity per Pack
WM100 Magnetic Cable Tie Mounts
WM25 Magnetic Cable Tie Mounts
WM5 Magnetic Cable Tie Mounts

Dimensions & Weight

Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weigtht: 54.3 Lbs. (24.6 kg).
  • Shipping Weigtht: 59.3 Lbs. (26.9 kg).