Specifications
eFlow104NB Power Supply/Charger
Input
- Voltage: 120VAC, 60Hz, 4.5A max.
- Input Fuse: 6.3A / 250V.
Outputs
- Voltage: 24VDC @ 10A.
- Auxiliary: 1A (unswitched).
- Protection: Overvoltage protection. Filtered and regulated.
Battery Charging
- Type: Sealed lead acid or gel type.
- Fuse Rating: 15A @ 32VDC.
- Failover: Upon AC loss, instantaneous.
- (Batteries are sold separately).
Fire Alarm Disconnect
- Supervised: Latching or non-latching.
- EOL: 10K Resistor.
Supervision
- AC Failure: Form “C” contacts.
- Battery: Form “C” contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Indicators LED
- AC Input: 120VAC is present.
- DC Output: Powered.
- Battery: Discharged or not connected.
VR6 Voltage Regulator
Input
- Voltage: 24VDC from eFlow104NB.
Output
- Voltage: 12VDC.
- Current: 6A continuous.
- Other: Surge suppression.
Indicators LED
- Input: 24VDC is present.
- Output: Powered.
LINQ8PDCB Network Power Distribution Module
Input
- Voltage: 24VDC from eFlow104NB and 5VDC or 12VDC from VR6.
- Input Fuse: 15A / 32V.
Outputs
- Eight (8) PTC protected outputs rated 2A.
- Power output(s) can be locally or remotely controlled.
- Surge suppresion.
- Output PTCs: 2A.
Status Monitoring
- Power Supply output voltage and load.
- Voltage and load of each output.
- FACP trigger and reset status.
- Unit temperature (Celsius).
- Power Supply AC and Battery status.
- Battery health.
Indicators (LED)
- Bat Local: Charging current status.
- FACP: Triggered / Released.
- Input: Input signal.
- Out1 - Out8: Bi-colored LEDs indicate 12 or 24VDC.
Reporting
- Windows Dashboard Alert messages.
- E-mail notifications.
- Event Log tracks history.
Programming Features
- Power Supply(ies) voltage and load limits (High/Low).
- FACP trigger type (wet or dry-N.O./N.C.).
- Input Function (FACP reset/tamper).
- Output Reset Trigger (N.O./N.C.).
- Battery Monitor Configuration:
- - Battery condition (Low/Normal/Missing)
- - Service Date
- Configurable Output Relay(s).
- Individual Output Configuration:
- - Device ID
- - Voltage and Current Limits (High/Low)
- - FACP Trigger Setting (latching/non-latching/inactive)
- - Battery Backup.
Fire Alarm Interface
- Supervised FACP disconnect (Latching or Non-Latching).
- FACP reset (N.C. or N.O.).
Environmental
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Dimensions 12"W x 15.5"H x 4.5"D (304.8 mm W x 393.7 mm H x 114.3 mm D).
- 1.125" and 1.375" combination knockouts.
Weights (approximate):
- Product Weigtht: 9.4 Lbs. (4.26 kg).