Specifications
eFlow104NB Power Supply/Charger
Input
- Voltage: 120VAC, 60Hz, 4.5A max.
- Input Fuse: 6.3A / 250V.
Outputs
- Voltage: 24VDC @ 10A.
- Auxiliary: 1A (unswitched).
- Protection: Overvoltage protection. Filtered and regulated.
Battery Charging
- Type: Sealed lead acid or gel type.
- Fuse Rating: 10A @ 32VDC.
- Failover: Upon AC loss, instantaneous.
- (Batteries are sold separately).
Fire Alarm Disconnect
- Supervised: Latching or non-latching.
- EOL: 10K Resistor.
Supervision
- AC Failure: Form “C” contacts.
- Battery: Form “C” contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
Indicators LED
- AC Input: 120VAC is present.
- DC Output: Powered.
- Battery: Discharged or not connected.
VR6 Voltage Regulator
Input
- Voltage: 24VDC from eFlow104NB.
Output
- Voltage: 12VDC.
- Current: 6A continuous.
- Other: Surge suppression.
Indicators LED
- Input: 24VDC is present.
- Output: Powered.
LINQ8ACM Network Access Power Controller
Input
- Voltage: 24VDC from eFlow104NB and 12VDC or 5VDC from VR6.
- Input Fuses: 15A / 32V.
Outputs
- Fuse protected outputs rated @ 2.5A per output, non power-limited. Total output 20A max.
- Any of the eight (8) fuse protected power outputs are selectable to follow power Input 1 or Input 2.
- Individual outputs may be set to OFF position for servicing.
- Output Fuses: 3A / 32VDC.
Programming Features
Eight (8) Programmable Outputs
- - Fail-safe, fail-secure or auxiliary outputs.
- - Input controlled or manually controlled through software.
- - High (over) and low (under) voltage and current monitoring by output.
- - Multiple outputs may be programmed to be triggered by a single input.
- - Battery back-up by output.
Eight (8) Programmable Trigger Inputs
- - Normally open (NO).
- - Normally closed (NC).
- - Open collector sink inputs.
- - Wet Input (5VDC - 24VDC) with 10k resistor.
- - Any combination of the above.
Other Programmable Trigger Inputs
- - Monitor power supply(ies) input for voltage and current limits (high/low).
- - Input and output current calibration.
- - Programmable timer events.
- - Programmable user levels.
- - Enable or disable alerts by type.
- - Programmable alert reporting delay.
Fire Alarm Disconnect
- Supervised: Inactive, latching or non-latching, individually selectable for any or all of the eight (8) outputs.
- EOL: 10K Resistor.
LED Indicators
- Green AC LED: indicates AC trouble condition.
- Green BAT LED: indicates battery trouble condition.
- Green FACP LED: indicates FACP disconnect is triggered.
- Flashing Blue Heartbeat LED: indicates network connection.
- Individual OUT1 - OUT8 Red LEDs: indicate outputs are triggered.
- Out1 - Out8: Bi-colored LEDs indicate 12 or 24VDC.
Environmental
Temperature
- Operating: 0° C to 49° C (32° F to 120° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity
- Relative Humidity: 85% +/- 5%.
BTU/Hr. (approx.):
Dimensions & Weight
Enclosure:
- Wall mount enclosure for indoor use.
- Accommodates up to two (2) 12VDC/12AH Batteries.
- Dimensions 12"W x 15.5"H x 4.5"D (304.8 mm W x 393.7 mm H x 114.3 mm D).
- 1.125" and 1.375" combination knockouts.
Weights (approximate):
- Product Weigtht: 9.4 Lbs. (4.26 kg).
- Shipping Weigtht: 10.5 Lbs. (4.76 kg).