AL1024NKA8DQM

Networked Dual Voltage Access Power Controller with Power Supply/Charger, BC400 Encloshure

Ordering# AL1024NKA8DQM Kit Contents: AL1024ULX with VR6 and LINQ8ACMCB UL Listed sub-assemblies

Altronix AL1024NKA8DQM sub-assembly kit converts a 115VAC 60Hz input into eight (8) PTC protected power limited outputs. Outputs are individually selectable, providing 12VDC or 5VDC up to 6A and/or 24VDC up to 10A (240W total power) for access control panels, door locks, and ancillary devices. Power outputs can be converted to dry form “C” contacts. Outputs are activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. AL1024NKA8DQM will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain power to multiple LINQ8ACM(CB) modules. This feature allows you to distribute the power over more outputs for larger systems. Built-in LINQTM Network Power Management facilitates monitoring, reporting and control of power/diagnostics.

  • AL1024ULXB2 Power Supply/Charger
      • Input
        • Voltage: 115VAC, 60Hz, 4.2A max.
        • Input Fuse: 5A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Current: 10A @ 24VDC continuous max.
        • Protection: Overvoltage protection. Filtered and regulated.
  • Battery Charging
    • Capacity: 12AH /12VDC (2 within enclosure); 40 AH / 65 AH (requires separate enclosure).
    • Type: Sealed lead acid or gel type.
    • Failover: Upon AC loss, instantaneous.
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators LED
    • Input: 115VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • VR6 Voltage Regulator
      • Input
        • Voltage: 24VDC from AL1024ULXB2.
      • Output
        • Voltage: 12VDC.
        • Current: 6A continuous.
        • Other: Surge suppression.
      • Indicators LED
        • Input: 24VDC is present.
        • Output: Powered.
  • LINQ8ACMCB Network Access Power Controller
      • Input
        • Voltage: 24VDC from AL1024ULXB2 and 12VDC from VR6.
        • Input PTCs: 9A.
      • Outputs
        • PTC protected outputs rated @ 2.5A per output, non power-limited.
        • Any of the eight (8) PTC protected power outputs are selectable to follow power Input 1 or Input 2.
        • Individual outputs may be set to OFF position for servicing.
        • Output PTCs: 2.5A.
  • Programming Features:
      • Eight (8) Programmable Outputs:
        • - Fail-safe, fail-secure or auxiliary outputs.
        • - Input controlled or manually controlled through software.
        • - High (over) and low (under) voltage and current monitoring by output.
        • - Multiple outputs may be programmed to be triggered by a single input.
        • - Battery back-up by output.
      • Eight (8) Programmable Trigger Inputs:
        • - Normally open (NO).
        • - Normally closed (NC).
        • - Open collector sink inputs.
        • - Wet Input (5VDC - 24VDC) with 10k resistor.
        • - Any combination of the above.
      • Other Programmable Trigger Inputs:
        • - Monitor power supply(ies) input for voltage and current limits (high/low).
        • - Input and output current calibration.
        • - Programmable timer events.
        • - Programmable user levels.
        • - Enable or disable alerts by type.
        • - Programmable alert reporting delay.
      • Fire Alarm Disconnect
        • Supervised: Inactive, latching or non-latching, individually selectable for any or all of the eight (8) outputs.
        • EOL: 10K Resistor.
      • LED Indicators
        • Green AC LED: indicates AC trouble condition.
        • Green BAT LED: indicates battery trouble condition.
        • Green FACP LED: indicates FACP disconnect is triggered.
        • Flashing Blue Heartbeat LED: indicates network connection.
        • Individual OUT1 - OUT8 Red LEDs: indicate outputs are triggered.
        • Out1 - Out8: Bi-colored LEDs indicate 12 or 24VDC.
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 123 BTU/Hr.
 
CE Compliant
 
Components of this kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to two (2) 12VDC/12AH Batteries.
  • Dimensions 12"W x 15.5"H x 4.5"D (304.8 mm W x 393.7 mm H x 114.3 mm D).
  • 1.125" and 1.375" combination knockouts.
Weights (approximate):
  • Product Weight: 9.4 Lbs. (4.26 kg).
  • Shipping Weight: 10.5 Lbs. (4.76 kg).
Print
*Batteries sold separately