R1042ULADA

Rack Mountable NAC Power Extender, 4 Class A or 4 Class B Outputs, 24VDC @ 10A, 120VAC, Red Trove1R Enclosure

Altronix R1042ULADA is a space-saving 10A remote power supply/battery charger for fire signaling applications such as Notification Appliance Circuits expansion (strobes and horns) meeting ADA requirements. The rack mount drawer configuration is designed to be deployed where wall space is limited or may not be an option. R1042UALDA may be connected to any 12 or 24 volt Fire Alarm Control Panel (FACP) and also provides auxiliary power to support system accessories. This unit delivers electronically regulated and filtered 24 volt power to Class B or Class A NAC loop circuits. The 10A max. alarm current can be divided between the four (4) outputs for powering NAC devices. All outputs may be programmed for Input to Output Follower Mode (output will follow input). Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs.

  • Input
      • Voltage:
        • 120VAC, 60Hz, 5A.
        • Two (2) Class A or two (2) Class B inputs.
        • Two (2) NC dry contact trigger inputs.
      • Input Ratings (INP1 and INP2):
        • 8-30VDC 6.5mA max from FACP.
        • 12V 6.5mA, 24V 6.5mA from FACP.
  • Output
      • Voltage:
        • 24VDC power-limited outputs.
      • Current:
        • 10A max. total alarm current.
        • 2.5A max. current per output.
      • Auxiliary:
        • Two auxiliary outputs rated at 1A each (1A continuous, 1A AC disconnect).
      • Other:
        • Thermal and short circuit protection with auto reset.
        • Filtered and regulated outputs.
      • Programmable Supervised Indicating Circuit Outputs:
        • Four (4) Class B, or Four (4) Class A, or
        • Two (2) and Two (2) Class B.
  • Battery Charging
    • Built-in charger for sealed lead acid or gel type batteries.
    • Automatic switchover to stand-by battery when AC fails.
    • Zero voltage drop when switching over to battery backup.
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators (LED)
    • AC Power (Green): Input voltage is present.
    • DC Output (Red): Powered.
    • Logic Board (Red and Green): Output status.
  • Special Features
    • 2-wire horn/strobe Sync mode allows audible notification appliances (horns) and visual notification appliances (strobes) to be silenced/deactivated at the same time.
    • Sync protocols include Potter/Amseco, Gentex®, System Sensor®, and CooperWheelock®.
    • Temporal Code 3, Steady Mode, Input to Output Follower Mode (maintains synchronization of notification appliances circuit).
    • Compatible with 12VDC or 24VDC fire panels.
    • Output loop supervision steered to Input 1 or Input 2.
    • Signal circuit trouble memory (helps identify intermittent loop problems).
    • Common trouble input and output for external trouble signals tie-in.
    • Ground fault detection.
  • Temperature
    • Operating: 0° C to 49° C (32° F to 120° F).
    • Storage: - 20° C to 70°C ( - 4° F to 158° F).
    • Relative Humidity: 85% +/- 5%.
    • BTU/Hr. (approx.): 31 BTU/Hr.
UL Listed For:
Control Units and Accessories for Fire Alarm Systems (UL864)
 
CSFM - California State Fire Marshal Approved
 
FM Approved
Enclosure:
  • Trove Rack Mount Enclosure
  • Dimensions 19"W x 3.25"H x 26.5"D (482.6 mm W x 82.6 mm H x 673.1 mm D).
  • Rails extend to 36" (914.4mm). Ample knockouts for convenient use.
Weights (approximate):
  • Product Weight: 20 Lbs. (9.07 kg).