T2KE3316

16-Door Altronix/Kisi Access and Power Integration Kit - Trove2DR2 with (2) AL600ULXB, (2) ACM8

News Flash… Altronix lead time for all Trove Access & Power Integration kits are now 15 days max.

Altronix T2KE3316 kit consists of Trove2 enclosure, TDR2 Kisi/Altronix backplane with two (2) 12 or 24VDC @ 6A power supply/chargers, and two eight (8) fuse protected output access control modules. This kit also accommodates up to four (4) Kisi Pro Controllers for up to sixteen (16) doors in a single enclosure. Trove simplifies board layout and wire management, reduces installation time and labor costs.

  • Two (2) AL600ULXB Power Supply/Chargers
      • Input
        • Voltage: 115VAC, 60Hz, 3.5A max.
        • Input Fuse: 5A / 250V.
      • Outputs
        • Voltage: 12VDC or 24VDC selectable.
        • Current: 6A @ 12VDC or 24VDC continuous max.
        • Other: Filtered and regulated.
  • Battery Charging
    • Capacity: 7AH/12VDC (Up to 4 within enclosure); 12AH / 12VDC (up to 4 within enclosure); 40 AH/65 AH (requires separate enclosure)
    • Type: Sealed lead acid or gel type
    • Failover: Upon AC loss, instantaneous
    • (Batteries are sold separately).
  • Supervision
    • AC Failure: Form “C” contacts.
    • Battery: Form “C” contacts.
  • Indicators LED
    • Input: 115VAC is present.
    • DC Output: Powered.
    • Battery: Discharged or not connected.
  • Two (2) ACM8 Access Power Controllers
      • Input
        • Voltage: 24VDC from AL600ULXB.
        • Input Fuse: 10A / 250V.
      • Outputs
        • Voltage: 24VDC.
        • Eight (8) 24VDC independently controlled fused outputs:
        • a) Fail-Safe and/or Fail-Secure power outputs Form “C” Relays rated 28VAC or VDC @ 2.5A
        • b) Auxiliary power outputs (unswitched).
        • c) Any combination of the above.
      • Outputs Ratings
        • Fuses: 3.5A/250V.
      • Indicators (LED's)
        • Red LEDs: Outputs are triggered (relays energized).
        • Green LED: FACP disconnect is triggered.
  • Environmental
      • Temperature
        • Operating: 0° C to 49° C (32° F to 120° F).
        • Storage: - 20° C to 70° C ( - 4° F to 158° F).
      • Relative Humidity
        • Relative Humidity: 85% +/- 5%.
      • BTU/Hr. (approx.):
        • 12VDC: 74 BTU/Hr
        • 24VDC: 148 BTU/Hr
        • 12VDC and 24VDC: 111 BTU/Hr
 
CE Compliant
 
Components of this Trove kit are UL Listed sub-assemblies. Please refer to the corresponding Sub-Assembly Installation Guides for further information. Sub-assembly components of this kit can be found under the "Kit Contents" tab.
Enclosure:
  • Wall mount enclosure for indoor use.
  • Accommodates up to four (4) 12VDC/12AH Batteries.
  • Dimensions 21.5"W x 27.25"H x 6.5"D (546.1 mm W x 692.15 mm H x 165.1 mm D).
  • 3/4" and 1" combination knockouts.
Weights (approximate):
  • Product Weight: 54.7 Lbs. (24.8 kg).
  • Shipping Weight: 59.7 Lbs. (27.1 kg).

Access controllers not included